Supermicro SYS-421GE-TNHR2-LCC

8 × H100 / H200 SXM5 per node, with 8 compute rails at 400G. That is 3.2 Tb/s of scale-out network per node.

What this means for the fabric

8 compute NICs means 8 rails. In a rail-optimized design each of those rails is sized on its own against the node count, then multiplied back up, so the leaf tier is driven by the rail count and not by the total endpoint count.

Storage and in-band management are separate fabrics with their own switches and their own optics, and the 1 BMC port per node feed the out-of-band network, which also has to carry every switch and every PDU in the cluster.

Power and racks

At 10.2 kW typical draw, this node fills a rack's power budget long before it fills the space. A 45 kW rack takes 4 of them on power alone, against 10 on rack units. Power is what actually sets the rack count.

Notes

Verified: 4U liquid-cooled HGX H100/H200 8-GPU on 5th/4th Gen Intel Xeon. Liquid cooling is what makes 4U viable at this power; density is still power-limited in most halls, so raise the rack budget to see the benefit.

Source: Supermicro SYS-421GE-TNHR2-LCC datasheet, verified 2026-08. Confirmed 2026-08-06